| EJX118A Diaphragm Sealed Differential Pressure Transmitter | |
M Capsule | H Capsule | |
Range | -100 to 100 kPa | -500 to 500 kPa |
(-400 to 400 inH2O) | (-2000 to 2000 inH2O) | |
Span | 2 to 100 kPa | 10 to 500 kPa |
(8 to 400 inH2O) | (40 to 2000 inH2O) | |
Accuracy | ±0.15% | ±0.15% |
Degrees of protection | IP67, NEMA 4X, and JIS C0920 immersion proof | |
Certificates | FM, CENELEC ATEX, CSA, IECEx | |
Output | 4 to 20 mA DC or FOUNDATION™ fieldbus, 2-wire system with digital communication | |
Supply voltage | BRAIN and HART:10.5 to 42 V DC | |
(10.5 to 30 V DC for Intrinsically safe type) | ||
Fieldbus:9 to 32 V DC | ||
(9 to 24 V DC for Entity and 9 to 17.5 V DC for FISCO) | ||
Ambient temperature | -40 to 60 deg C (-40 to 140 deg F) (general use type) | |
-30 to 60 deg C (-22 to 140 deg F) (with integral indicator) | ||
It must be within the fill fluid operating temperature range. | ||
Process temperature | -50 to 310 deg C (-58 to 590 deg F) | |
It must be within the fill fluid operating temperature range. | ||
Maximum working | Flange rating pressure | |
pressure | ||
Mounting | Transmitter: 2-inch pipe mounting | |
Diaphragm seals: flange mounting | ||
Process flange size | Flush type: | 3-inch (80 mm), 2-inch (50 mm), |
1 1/2-inch (40 mm) | ||
Extended type: | 4-inch (100 mm), 3-inch (80 mm) | |
Combination | 4-inch (100 mm) for extended high side, | |
type: | 3-inch (80 mm) for flush low side | |
Diaphragm material | SUS316L, Hastelloy C-276, Tantalum, Titanium | |
Process flange material | S25C, SUS304, SUS316 | |
Housing | Cast |